Thermal performance of an overhead transmission line under the influence of dust accumulation

Faculty Engineering Year: 2000
Type of Publication: Article Pages: 1323-1334
Authors: DOI: 10.1016/S0196-8904(99)00125-9
Journal: ENERGY CONVERSION AND MANAGEMENT PERGAMON-ELSEVIER SCIENCE LTD Volume: 41
Research Area: Thermodynamics; Energy \& Fuels; Mechanics; Physics ISSN ISI:000086807000008
Keywords : thermal rating, transmission line, conductor ampacity, temperature distribution, thermal effect, life time, dusty transmission lines    
Abstract:
The temperature distribution in the radial direction of a composite overhead transmission line in steady state is the main object of this work when a layer of dust or aluminium oxide is accumulated around the surface of the line. This undesirable dust accumulation will cause an additional rise in temperature of the line. Therefore, the hypothetical lifetime of the line will be reduced. A mathematical model has been developed, when the heat supplied to the dusty transmission line is balanced by the heat dissipated. to give the temperature of each layer of the line in addition to the dust layer temperature. A reduction coefficient of the life time of the line under the influence of dust accumulation is derived. The ampacity of the dusty line should be reduced in order that the temperature of the line doesn't exceed the maximum permissible temperature and to maintain the hypothetical life time of the line. The proposed reduction coefficient of the line ampacity will be, also, deduced. (C) 2000 Elsevier Science Ltd. All rights reserved.
   
  Online    
PDF  
       
Tweet